Brand: SHANGFANG
Model: sf-134
Features
Temperature Control
Manual/automatic defrost.
Time/temp.setting to end defrost
High,Low temperature alarm
Re-start delay
Self Testing
Parameter Locking
Technical Data
Range of temperature displayed:-45~150℃(-45~302℉)
Range of set temperature:-45~45℃(-45~120℉)
Accuracy:±1℃(±2℉)
Temperature sensing probe: two
Comperssor relay:Normally open 16A/250VAC
Defrost heating wire:Normally open 10A/250VAC
Evaporator fan:Normally open 5A/250VAC
Dimension:77mm(L)×35mm(W)×60mm(D)
Mounting hole dimensio:71mm(L)×29mm(W)
Parameters
Paramete | Function | Set range | Default |
E1 | Lower setpoint limit | -45℃/-45℉~Set temp. | -35℃/-31℉ |
E2 | Higher setpoint limit | Set temp.~100℃/212℉ | 20℃/68℉ |
E3 | Temp.hysteresis | 1~20℃/1~36℉ | 4℃/7℉ |
E4 | Comp.start delay time | 0~10Min | 2Min |
E5 | Offset on room temp. | -20~20℃/-36~36℉ | 0 |
E6 | Offset on evap.temp. | -20~20℃/-36~36℉ | 0 |
E7 | Offset on condens | -20~20℃/-36~36℉ | 0 |
F0 | Defrost function | 0=Electric heater 1=Hot gas | 0 |
F1 | Max.Defrost duration | 1~60Min | 20Min |
F2 | Defrost interval time | 0~24Hr | 4Hr |
F3 | Defrost termination temp. | 0~30℃/32~86℉ | 8℃/46℉ |
F4 | Display during defrost | 0=Normal display 1=Last value before defrost | 0 |
F5 | Fan operating function | 0=Parallel with comp. 1=Continuous running except defrost | 0 |
C1 | Temperature unit | ℃=Celsius ℉=Fahr. | ℃ |
C2 | High temperature alarm | C3~100℃/212℉ | 40℃/104℉ |
C3 | Low temperature alarm | -45℃/-45℉~C2 | -40℃/-40℉ |
C4 | Alarm delay time | 1~90Min | 60Min |